Which of the following tasks would be permitted without a completed energized electrical work permit?

Energized Diagnostic work, which includes only testing, troubleshooting, voltage or current measurement and visual inspection may be done without an energized work permit provided ALL the following apply: An arc flash hazard assessment has been done to determine approach boundaries and PPE.

What is the purpose of an energized work permit?

It’s a written permit to work for an electrical worker to use when he or she is doing something that normally could be done on de-energized equipment. This can also act as a management tool to stop people from working energized when they don’t need to be.

Which of the following is a requirement when performing energized electrical work?

When it is necessary to perform work on energized equipment, OSHA 1910.333(a)(2) requires safety-related work practices to be used and NFPA 70E Article 110.8(B)(1) requires an Electrical Hazard Analysis before work is performed on live equipment operating at 50 volts and higher.

IT IS INTERESTING:  Can I convert my towel rail to electric?

Who is permitted to work on electrical conductors or circuit parts that have not been put into an electrically safe work condition?

When electrical conductors and circuits over 50 volts cannot be placed into an electrically safe work condition, and work is performed as permitted in accordance with NFPA 70E Section 110.4, the following requirements must be met: Only qualified persons are permitted to work on electrical conductors or circuits that …

Which type of hazard assessment must be completed before working near exposed energized conductors or circuits?

Appropriate safety-related work practices must be determined before any person is exposed to the electrical hazards involved by using both shock risk assessment and arc flash risk assessment. The term exposed movable conductor is normally applied to overhead line conductors supported by poles.

What are the three limits of approach boundaries?

Under NFPA 70E, there are three boundaries that are observed—limited approach, restricted approach, (the shock protection boundaries) and arc flash boundary.

Is voltage testing considered energized work?

Testing for voltage, measuring current, or testing for absence of voltage is energized electrical work. Racking in or out power circuit breakers or installing temporary protective grounds is energized electrical work. Operating energized electrical equipment in a normal state is not energized electrical work.

Who is responsible for electrical safety in the workplace?

Both the Health & Safety at Work Act 1974 and the Electricity at Work Regulations 1989 state that employers are responsible for ensuring the health and safety of employees and members of the public on their site, and to ensure that they are not at risk from their work activities.

IT IS INTERESTING:  Quick Answer: Why electric field lines are called lines of force?

When using a utility locate service to identify underground utilities which of the following is true?

using a utility locate service to identify underground utilities is an exact science because. When using a utility locate service to identify underground utilities, the following is true: Locating underground utilities is NOT an exact science. This answer has been confirmed as correct and helpful.

Is NFPA 70 the same as NEC?

NFPA 70®, National Electrical Code® (NEC®), sets the foundation for electrical safety.

Is arc flash an electrical hazard?

A dangerous condition such that contact or equipment failure can result in electric shock, arc flash burn, thermal burn, or blast. Fire, shock, and electrocution have been considered to be electrical hazards for many years. Since the 1995 edition of NFPA 70E, arc flash has been recognized as an electrical hazard.

What is the minimum approach distance for an unqualified person who is wearing appropriate PPE?

Best practice if for any unqualified person to stay 42” (3′ 6”) or more away from the hazard. A qualified person should use protective shields and barriers to protect employees working within the LAB.

Is PPE required for resetting a breaker?

In NFPA 70E table 130.7 it is stated that normal operation of a well-functioning circuit breaker/contactor does not require any PPE (unless there open doors/covers). And the conclusion is that there is no need for Arc protection as longs as everything is working correct.

What are some electrical hazards?

What are Examples of Electrical Hazards?

  • Contact with live wires resulting in electric shock and burns,
  • Fires due to faulty wiring,
  • Exposed electrical parts,
  • Ignition of fires or explosions due to electrical contact with potentially flammable or explosive materials,
  • Inadequate wiring,
IT IS INTERESTING:  What are the three types of energy used in cleaning?

What is arc flash hazard?

Simply put, an arc flash is a phenomenon where a flashover of electric current leaves its intended path and travels through the air from one conductor to another, or to ground. … Because of the violent nature of an arc flash exposure when an employee is injured, the injury is serious – even resulting in death.

What is considered electrical hot work?

Hot work is the practice of working on energized electrical circuits (voltage limits differ regionally) – and it is usually done, in spite of the risks, to reduce the possibility of a downtime incident during maintenance. Uptime Institute advises against hot work in almost all instances.